Metal Roof with Cathedral Ceiling above Rafters (exposed beams)
ICANZ System Reference R0500
Structure
Tiled cathedral roof at 22.5o pitch, with foil draped under tile batten providing 40mm air space with bright side of foil facing downward. Tile battens fixed over counter batten providing minimum 70mm airspace. 10mm plasterboard ceiling fixed under counter batten but over exposed roof rafter.
Insulation Installation
Option 1: Single sided polyweave foil positioned over batten. Reflective polystyrene positioned at mid height of original 70mm air space providing 20mm air space above and below reflective EPS board.
Option 2: Single sided polyweave foil positioned over batten. Original 70mm air space below single sided polyweave foil replaced with 20mm air space and R1.5 - 50mm bulk insulation. Bulk insulation on the ceiling lining.
NOTE: Total R-Values can be increased by substituting bulk insulation products of higher Material R-Value.