R0600 Metal Roof with Cathedral Ceiling above Rafters

Structure

ICANZ system reference for this roof is R0600 - Metal cathedral roof at between 18 degrees and 35 degrees of pitch with with R1.8 roofing blanket adhered to RFL vapour barrier foil product draped over 110mm high battens which are located over ceiling lining and roof rafter. Foil facing downwards to minimum 15mm air space, and 10mm plasterboard ceiling fixed between batten and exposed rafter.

 Metal Roof with Cathederal Ceiling above Rafters

Installation

NOTE: Total R-Values can be increased by substituting bulk insulation products of higher Material R-Value.

 Specifications - Metal roof, cathedral ceiling above rafters

A. Calculations assumptions in accordance with AS/NZS 4859.1:2002.  Amendment 1. 2006. Amendment 1. 2006 on the path of the insulation, as required by the BCA Vol 1. Part J and Vol 2. Section 3.12.
B. Temperatures and parameters are based on Australian climate assumptions. Air temperature difference 12oC (36oC less 24oC) for summer conditions and 6oC difference (18oC less 12oC) for winter.
C. Thermal resistance of air films and attic spaces based on values obtained from Section K5 and K6 of AS 4859.1:2006.
D. Building material elements based on 2000 AIRAH Handbook and attic thermal value based on AS4859.1 app K6 table K2.
E. Where reflective insulation is installed, a simple addition of R-values is not possible. Care must be taken to ensure the performance of reflective air spaces is not “double-counted”.
F. The emittance of the reflective surfaces are dependent on tested values and the conditions of the installation, as specified by AS/NZS 4859.1. Amendment 1. 2006.