R0600 Metal Roof with Cathedral Ceiling above Rafters
Structure
ICANZ system reference for this roof is R0600 - Metal cathedral roof at between 18 degrees and 35 degrees of pitch with with R1.8 roofing blanket adhered to RFL vapour barrier foil product draped over 110mm high battens which are located over ceiling lining and roof rafter. Foil facing downwards to minimum 15mm air space, and 10mm plasterboard ceiling fixed between batten and exposed rafter.

Installation
- Option 1: Double sided antiglare foil over minimum 110mm batten. Remaining 70mm air space below double sided antiglare foil replaced with 20mm air space and R1.5 - 50mm, bulk insulation. Bulk insulation positioned over 10mm plasterboard ceiling fixed between batten and exposed roof rafter.
- Option 2: Double sided antiglare foil over minimum 110mm batten. Reflective EPS board positioned at mid height of remaining 70mm air space providing 20mm airspace above and below reflective EPS board.
- Option 3: Polyweave or double sided antiglare foil draped over 90mm batten (40mm airspace above, 50mm airspace below).
NOTE: Total R-Values can be increased by substituting bulk insulation products of higher Material R-Value.